Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T15BU01311
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2016 | FIRE - ALARM FINAL | Approved | ||
11/19/2015 | FIRE - ALARM FINAL | Partial Approval | on Phase 1 Sam Levitz side Tested and Passed duct detectors on roof ( 4) - signals received supervisory smokes ( 2) above FACP and Aux Power unit second floor - signals received Flow #1 - 38 Sec signals received #2 - 48 sec signals received Tamper #1 working - siganls received #2 working - signals received #3 working - signals received pull station - working - signals received Horn / Strobes - working and devices as per plan FACP - power out - batteries working - signal received batter disconnect - working - signal received |