Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
08/18/2015
Applicant:
METRO TUCSON EXPEDITING & DEVELOPMENT
Description:
161 LF OF C-900 4 INCH UNDERGROUND FIRE LINE
Contractors:
  • DESERT EARTH CONTRACTING L L C

Outstanding Activity Conditions

Permit Number - T15BU00951
Permit Status: Expired
Permit Description: 161 LF OF C-900 4 INCH UNDERGROUND FIRE LINE
Total Outstanding Activity Conditions - 1
Date Name
08/18/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T15BU00951
Permite Description: 161 LF OF C-900 4 INCH UNDERGROUND FIRE LINE
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
FIRE SPKLR - FINAL N/A Not Inspected
08/27/2015 FIRE SPKLR - UG PIPING FLUSH N/A Denied NEEDS TO BE FLUSHED

Completed Inspections

Permit Status: Expired
Permit Number: T15BU00951
Permit Description: 161 LF OF C-900 4 INCH UNDERGROUND FIRE LINE
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/27/2015 FIRE SPKLR - UG, PIPING, HYDRO CSCHULTZ Approved 200 psi for 2 hours
This 4" C-900 underground piping was installed in the ground for potential use in the future as a cost savings. Still needs to be flushed after piping is connected to the city water main.

Thrust blocks in tracer wire in place and all metal fittings cover with plastic wrap, 45 deg was added to keep piping away from handicap ramp area on the east end.

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW