Permit: T15BU00951

Parcel: 127121200


Addresses:

5601 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
08/27/2015 FIRE SPKLR - UG, PIPING, HYDRO Approved 200 psi for 2 hours
This 4" C-900 underground piping was installed in the ground for potential use in the future as a cost savings. Still needs to be flushed after piping is connected to the city water main.

Thrust blocks in tracer wire in place and all metal fittings cover with plastic wrap, 45 deg was added to keep piping away from handicap ramp area on the east end.