Permit: T15BU00872
Permit Details
Apply Date:
07/30/2015
Applicant:
CENTRAL ALARM OF TUCSON** APA
Description:
FIRE ALARM
Contractors:
- CENTRAL ALARM OF TUCSON** APA
Outstanding Activity Conditions
Permit Number - T15BU00872
Permit Status: Expired
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/30/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T15BU00872
Permite Description: FIRE ALARM
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2015 | FIRE - ALARM FINAL | N/A | Denied | The following was inspected: A/C FAILED - PASSED FLOW SWITCH 41SEC - PASSED PULL STATION - PASSED SMOKE ABOVE PANEL - PASSED TAMPER VALVE - PASSED MISSING BATTERY - PASSED BREAKER LOCK ON - PASSED Fire alarm system failed due to two hood systems that are installed and approx. 4 duct detectors are not being monitored, advise the alarm company they will need to resubmitted plans showing all changes. |