Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
07/30/2015
Applicant:
CENTRAL ALARM OF TUCSON** APA
Description:
FIRE ALARM
Contractors:
  • CENTRAL ALARM OF TUCSON** APA

Outstanding Activity Conditions

Permit Number - T15BU00872
Permit Status: Expired
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date Name
07/30/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T15BU00872
Permite Description: FIRE ALARM
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
08/10/2015 FIRE - ALARM FINAL N/A Denied The following was inspected:
A/C FAILED - PASSED
FLOW SWITCH 41SEC - PASSED
PULL STATION - PASSED
SMOKE ABOVE PANEL - PASSED
TAMPER VALVE - PASSED
MISSING BATTERY - PASSED
BREAKER LOCK ON - PASSED
Fire alarm system failed due to two hood systems that are installed and approx. 4 duct detectors are not being monitored, advise the alarm company they will need to resubmitted plans showing all changes.

Documents

File Name Document Type  
None FIRE PLANS VIEW