Permit: T15BU00872

Parcel: 12810069C


Addresses:

436 S WILLIAMS BL

Inspection Status: Denied

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
08/10/2015 FIRE - ALARM FINAL Denied The following was inspected:
A/C FAILED - PASSED
FLOW SWITCH 41SEC - PASSED
PULL STATION - PASSED
SMOKE ABOVE PANEL - PASSED
TAMPER VALVE - PASSED
MISSING BATTERY - PASSED
BREAKER LOCK ON - PASSED
Fire alarm system failed due to two hood systems that are installed and approx. 4 duct detectors are not being monitored, advise the alarm company they will need to resubmitted plans showing all changes.