Permit: T15BU00769
Permit Details
Apply Date:
07/02/2015
Applicant:
WESTERN STATES FIRE PROTECTION C
Description:
FIRE ALARM
Contractors:
- WESTERN STATES FIRE PROTECTION C
- WESTERN STATES FIRE PROTECTION C **APA**
Outstanding Activity Conditions
Permit Number - T15BU00769
Permit Status: Final
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/02/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU00769
Permit Description: FIRE ALARM
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2015 | FIRE - ALARM FINAL | nsprenger | Approved | 1. Remove old smoke detectors not tied into the system. 2. Remove manual door stops on doors. ( There are already electronic door stops and they release when then alarm system is activated. 3. lower pull station so that it is not blocked by panel. 4. lock out breaker # 7 ( FAP breaker) 5. Cap wires in ceiling from old smoke that was removed. 6. Alarms system must be monitored per 2012 IFC 907.6 All appliances per plan. All smokes were tested and approved. All pull stations were tested an approved. Still need to verify signals once system is set up to be monitored. NS |