Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2016 | FIRE - ALARM FINAL | Approved | SYSTEM IS NOW MONITORED; SIGNALS REPORTED CORRECTLY. | |
| 09/10/2015 | FIRE - ALARM FINAL | Partial Approval | 1. Remove old smoke detectors not tied into the system. 2. Remove manual door stops on doors. ( There are already electronic door stops and they release when then alarm system is activated. 3. lower pull station so that it is not blocked by panel. 4. lock out breaker # 7 ( FAP breaker) 5. Cap wires in ceiling from old smoke that was removed. 6. Alarms system must be monitored per 2012 IFC 907.6 All appliances per plan. All smokes were tested and approved. All pull stations were tested an approved. Still need to verify signals once system is set up to be monitored. NS |