Permit: T15BU00769

Parcel: 13422115C


Addresses:

6840 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
01/27/2016 FIRE - ALARM FINAL Approved SYSTEM IS NOW MONITORED; SIGNALS REPORTED CORRECTLY.
09/10/2015 FIRE - ALARM FINAL Partial Approval 1. Remove old smoke detectors not tied into the system.
2. Remove manual door stops on doors. ( There are already electronic door stops and they release when then alarm system is activated.
3. lower pull station so that it is not blocked by panel.
4. lock out breaker # 7 ( FAP breaker)
5. Cap wires in ceiling from old smoke that was removed.
6. Alarms system must be monitored per 2012 IFC 907.6

All appliances per plan. All smokes were tested and approved. All pull stations were tested an approved. Still need to verify signals once system is set up to be monitored.
NS