Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
1130 W MIRACLE MILE
Apply Date:
06/30/2015
Applicant:
SOUTHERN ARIZONA FIRE PROTECTION SERVICES LLC
Description:
13R SYSTEM FOR 2 BUILDINGS
Contractors:
  • SOUTHERN ARIZONA FIRE PROTECTION SERVICES LLC

Outstanding Activity Conditions

Permit Number - T15BU00749
Permit Status: Expired
Permit Description: 13R SYSTEM FOR 2 BUILDINGS
Total Outstanding Activity Conditions - 1
Date Name
06/30/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T15BU00749
Permite Description: 13R SYSTEM FOR 2 BUILDINGS
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
FIRE SPKLR - UG PIPING FLUSH N/A Not Inspected
06/27/2016 FIRE SPKLR - FINAL N/A Cancelled IVRS - RI canceled
10/26/2015 FIRE SPKLR - UG, PIPING, HYDRO N/A Partial Approval Bldg. #1 UG done 200 PSI for 2 hours needs tracer wire installed
Bldg.#2 Partial approval UG part only and was tested 200 PSI for 2 hours, still need UG piping installed over building to riser and needs to be tested at 200 PSI for 2 hours again. OKAY to bury UG piping still needs tracer wire installed.

Completed Inspections

Permit Status: Expired
Permit Number: T15BU00749
Permit Description: 13R SYSTEM FOR 2 BUILDINGS
Total Completed Inspections - 1
Date Description Inspector Results Comments
06/10/2016 FIRE SPKLR - OH PIPING & HYDRO CBASALDUA Approved

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
002_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW