Permit: T15BU00749

Parcel: 10706008A


Addresses:

1130 W MIRACLE MILE


Inspection Status: Partial Approval

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T15BU00749

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Partial Approval

Date Description Inspector Results Comments
10/26/2015 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Bldg. #1 UG done 200 PSI for 2 hours needs tracer wire installed
Bldg.#2 Partial approval UG part only and was tested 200 PSI for 2 hours, still need UG piping installed over building to riser and needs to be tested at 200 PSI for 2 hours again. OKAY to bury UG piping still needs tracer wire installed.