Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
03/13/2015
Applicant:
CUTLER FIRE PROTECTION INC ,
Description:
ADD 8 RELOCATE 14 SPRINKLERS
Contractors:
  • CUTLER FIRE PROTECTION INC ,

Outstanding Activity Conditions

Permit Number - T15BU00274
Permit Status: Expired
Permit Description: ADD 8 RELOCATE 14 SPRINKLERS
Total Outstanding Activity Conditions - 1
Date Name
03/13/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T15BU00274
Permite Description: ADD 8 RELOCATE 14 SPRINKLERS
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/16/2015 FIRE SPKLR - FINAL N/A Denied Still have a head with paint on it (dining area near restrooms on the side of bar
head in bar needs to be 12 inches away from the duct work ( 4 inches wide) below it.
cant find upright in ceiling
upright in ceiling near the cookline is covered by insulation and the throw appears to be blocked by a beam.

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW