Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15BU00274
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2015 | FIRE SPKLR - FINAL | Denied | Still have a head with paint on it (dining area near restrooms on the side of bar head in bar needs to be 12 inches away from the duct work ( 4 inches wide) below it. cant find upright in ceiling upright in ceiling near the cookline is covered by insulation and the throw appears to be blocked by a beam. |
|
06/12/2015 | FIRE SPKLR - FINAL | Denied | DENIED Sprinkler company shall submit as builds and place heads: 1. Missing tap 2. Need coverage between drop ceiling and over two freezers. 3. Missing two uprights in Kitchen on South East corner above drop ceiling near hoods. 4. Change plans to reflect that one head in women's restroom over toilets is still an upright 5. Must have 12 inches between pendant in bar and 4 inch duct work below ( 3 times rule). 6. replace painted over heads in bar and directly North of bar in dining. 7. remove tape from heads in bar 8. Provide results of last sprinkler system inspection to include the last 5 yr check valve test. 9. Replace missing cap on FDC on NW corner of parking lot. |