Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
02/12/2015
Applicant:
TYCO INTEGRATED SECURITY LLC
Description:
FIRE ALARM-ADD 5 DEVICES FOR WATERFLOW AND TAMPERS
Contractors:
  • TYCO INTEGRATED SECURITY LLC

Outstanding Activity Conditions

Permit Number - T15BU00167
Permit Status: Final
Permit Description: FIRE ALARM-ADD 5 DEVICES FOR WATERFLOW AND TAMPERS
Total Outstanding Activity Conditions - 1
Date Name
02/12/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T15BU00167
Permit Description: FIRE ALARM-ADD 5 DEVICES FOR WATERFLOW AND TAMPERS
Total Completed Inspections - 1
Date Description Inspector Results Comments
03/26/2015 FIRE - ALARM FINAL Nsprenger Approved Waterflow alarm at 24 seconds - alarm recieved
pull station at 1705 address ( control panel room) - alarm recieved
pull station at 1715 address ( reported to control panel at 1705) - alarm recieved
smoke in zone 2 ( alarm control panel room) panel reported and monitoring company recieved.
Battery dc'd and 12 seconds to report - Trouble alarm recieved
AC power loss - 5 second local trouble signal and switched to battery power.
Main valve is locked out - no supervisory tamper switch.