Permit: T15BU00167

Parcel: 13507461C


Addresses:

1715 S RESEARCH LP


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T15BU00167

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/26/2015 FIRE - ALARM FINAL Approved Waterflow alarm at 24 seconds - alarm recieved
pull station at 1705 address ( control panel room) - alarm recieved
pull station at 1715 address ( reported to control panel at 1705) - alarm recieved
smoke in zone 2 ( alarm control panel room) panel reported and monitoring company recieved.
Battery dc'd and 12 seconds to report - Trouble alarm recieved
AC power loss - 5 second local trouble signal and switched to battery power.
Main valve is locked out - no supervisory tamper switch.
03/20/2015 FIRE - ALARM FINAL Denied Power to the Fire Alarm Control Panel was not on a dedicated circuit. Was connected to a powerstrip plugged into the wall.
They need a dedicated power line that is locked out at the breaker panel.
NS 3/20/15