Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2015 | FIRE - ALARM FINAL | Approved | Waterflow alarm at 24 seconds - alarm recieved pull station at 1705 address ( control panel room) - alarm recieved pull station at 1715 address ( reported to control panel at 1705) - alarm recieved smoke in zone 2 ( alarm control panel room) panel reported and monitoring company recieved. Battery dc'd and 12 seconds to report - Trouble alarm recieved AC power loss - 5 second local trouble signal and switched to battery power. Main valve is locked out - no supervisory tamper switch. |
|
| 03/20/2015 | FIRE - ALARM FINAL | Denied | Power to the Fire Alarm Control Panel was not on a dedicated circuit. Was connected to a powerstrip plugged into the wall. They need a dedicated power line that is locked out at the breaker panel. NS 3/20/15 |