Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
5324 E 1ST ST 12
Address NEW:
5324 E 1ST ST 12
Apply Date:
01/22/2015
Applicant:
VICTOR ROSS
Description:
ALARM
Contractors:
  • CLIMATEC BUILDING TECHNOLOGIES GROUP

Outstanding Activity Conditions

Permit Number - T15BU00073
Permit Status: Expired
Permit Description: ALARM
Total Outstanding Activity Conditions - 1
Date Name
01/22/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T15BU00073
Permite Description: ALARM
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
04/23/2015 FIRE - ALARM FINAL N/A Partial Approval This job is broken up into 2 phases:
Phase 1 is the kitchen area storage room and outside bathrooms
Partial Approval given - OKAY to use the kitchen -Phase #1 approved
The following was completed and passed for Phase #1:
1. Duct smokes
2. Smoke above NAC panel
3. Pull stations
4. Horns and strobes
5. Dated batteries in NAC
6. NAC electrical panel labeled
The following will need to be done before phase #2 final will be given:
1. Need lock out installed on breaker for the alarm NAC
2. Need lock out installed on breaker for the fire Bell

Documents

File Name Document Type  
001_ALARM.TIF FIRE PLANS VIEW
002_ALARM.TIF FIRE PLANS VIEW
003_ALARM.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW