Permit: T14CM07795
Permit Details
Apply Date:
11/13/2014
Applicant:
RITEWAY VENTILATING *APA*
Description:
REPL SPLIT SYSTEM/GAS (APA)
Contractors:
- RITEWAY VENTILATING *APA*
Outstanding Activity Conditions
Permit Number - T14CM07795
Permit Status: Final
Permit Description: REPL SPLIT SYSTEM/GAS (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/13/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T14CM07795
Permit Description: REPL SPLIT SYSTEM/GAS (APA)
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2014 | MECHANICAL - FINAL | WLAHR | Approved | - TAMPER-PROOF CAPS NEEDED CONNECCTION OF LINESET TO COMPRESSOR - UNABLE TO VERIFY ALUMINUM CONNECTION TO COPPER CONDUCTORS IN JUCTION BOX FOR LISTED CONNECTORS - EXISTING ALUMINUM CONDUCTORS UNDERSIZED FOR 60 AMP OVERCURRENT PROTECTION |
| 12/12/2014 | MECHANICAL - FINAL | WLAHR | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 12/12/2014 | MECHANICAL - INTERMEDIATE | WLAHR | Approved | IVRS - Inspection : See detailed listing on site.| 999* |