Permit Details

Status:
L of c
Type:
COMMERCIAL ALTERATION
Address:
5301 E GRANT RD
Apply Date:
05/29/2014
Applicant:
DOUG HAWKINS
Description:
EXTERIOR RENOVATION - TMC R1-HELICAL PIER INSTALLATION
Architects:
  • POSTER, CHARLES MARCUS
Contractors:
  • BARKER MORRISSEY CONTRACTING INC **APA**

Permit Reviews

Permit Number - T14CM03220
Permit Status: L of c
Permit Description: EXTERIOR RENOVATION - TMC R1-HELICAL PIER INSTALLATION
Start Date Submittal Complete Date Status  
05/29/2014 COMMERCIAL - TI 06/26/2014 COMPLETED Review Details
08/14/2014 REVISION - - 1ST 08/28/2014 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T14CM03220
Permit Status: L of c
Permit Description: EXTERIOR RENOVATION - TMC R1-HELICAL PIER INSTALLATION
Total Outstanding Activity Conditions - 1
Date Name
05/29/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: L of c
Permit Number: T14CM03220
Permit Description: EXTERIOR RENOVATION - TMC R1-HELICAL PIER INSTALLATION
Total Completed Inspections - 17
Date Description Inspector Results Comments
08/27/2014 PLUMBING - ABOVE CEILING BBENEDON Approved
08/27/2014 PLUMBING - INTERMEDIATE BBENEDON Approved
09/24/2014 STUCCO MESH BBENEDON Approved IVRS - Inspection :*
09/30/2014 PLUMBING - GAS PRESSURE TEST BBENEDON Approved IVRS - Inspection :*
10/01/2014 GAS CLEARANCE BBENEDON Approved
12/09/2014 MECHANICAL - INTERMEDIATE BBENEDOI Approved IVRS - Inspection :*
12/09/2014 PLUMBING - FINAL BBENEDOI Approved IVRS - Inspection :*
12/09/2014 PLUMBING - PROGRESS BBENEDOI Approved IVRS - Inspection :*
12/09/2014 ELECTRIC - FINAL BBENEDOI Approved IVRS - Inspection :*
12/09/2014 ELECTRIC - OUTDOOR LIGHTING BBENEDOI Approved IVRS - Inspection :*
12/09/2014 ELECTRIC - INTERMEDIATE BBENEDOI Approved IVRS - Inspection :*
12/09/2014 FRAMING BBENEDOI Approved IVRS - Inspection :*
12/10/2014 FIRE - FINAL CSCHULTZ Approved Temp C of O (Partial approval) given for south wing legal department and a contactors office only
According to a TMC reprehensive Mr. Matthew Maynard stated that were told from system engineering section that the fire alarm system that was install years ago can be remove since the building is now used as a group "B" and does not need an alarm system. Mr. Maynard did then state they are going to monitored the sprinkler system for water flow and tamper (sprinkler is in the basement only 15 heads).
I did advise Mr. Maynard that they will need to remove all pull stations, smokes and anything that has anything to do with the old alarm system. If they are installing a new monitoring system that they will need to have an approved plan and permit before installation, also advise him that a smoke and pull station will be need for the new fire alarm monitoring system.
According to IFC 903.4 Exception #2 - states "Limited area systems serving fewer than 20 sprinklers" a monitoring system is not required. So they do not need to install a monitoring system but they do need a WMG or outside electric bell but TMC wants to install a monitoring system and they will need an approved plans and permits for this (IFC 105.7.6).
Need to fire patch all holes on the ceiling in the basement.
12/10/2014 FIRE SPKLR - FINAL CSCHULTZ Approved Sprinkler is in the basement only and has only 15 heads on the system, checked basement out no problems.
12/10/2014 FIRE - ALARM FINAL CSCHULTZ Approved Temp C of O (Partial approval) given for south wing legal department and a contactors office only
According to a TMC reprehensive Mr. Matthew Maynard stated that were told from system engineering section that the fire alarm system that was install years ago can be remove since the building is now used as a group "B" and does not need an alarm system. Mr. Maynard did then state they are going to monitored the sprinkler system for water flow and tamper (sprinkler is in the basement only 15 heads).
I did advise Mr. Maynard that they will need to remove all pull stations, smokes and anything that has anything to do with the old alarm system. If they are installing a new monitoring system that they will need to have an approved plan and permit before installation, also advise him that a smoke and pull station will be need for the new fire alarm monitoring system.
According to IFC 903.4 Exception #2 - states "Limited area systems serving fewer than 20 sprinklers" a monitoring system is not required. So they do not need to install a monitoring system but they do need a WMG or outside electric bell but TMC wants to install a monitoring system and they will need an approved plans and permits for this (IFC 105.7.6).
12/11/2014 MECHANICAL - FINAL BBENEDOI Approved IVRS - Inspection :*
12/11/2014 BUILDING - FINAL BBENEDOI Approved IVRS - Inspection :*

Documents

File Name Document Type  
001_G1.0.TIF CONSTRPLANS VIEW
002_A1.0.TIF CONSTRPLANS VIEW
003_A2.0.TIF CONSTRPLANS VIEW
004_A2.1.TIF CONSTRPLANS VIEW
005_A2.2.TIF CONSTRPLANS VIEW
006_A2.3.TIF CONSTRPLANS VIEW
007_A3.0.TIF CONSTRPLANS VIEW
008_A3.1.TIF CONSTRPLANS VIEW
009_A3.2.TIF CONSTRPLANS VIEW
010_A3.3.TIF CONSTRPLANS VIEW
011_A3.4.TIF CONSTRPLANS VIEW
012_A4.0.TIF CONSTRPLANS VIEW
013_P1.1.TIF CONSTRPLANS VIEW
014_P1.2.TIF CONSTRPLANS VIEW
015_P2.1.TIF CONSTRPLANS VIEW
016_M1.1.TIF CONSTRPLANS VIEW
017_M1.2.TIF CONSTRPLANS VIEW
018_M2.1.TIF CONSTRPLANS VIEW
019_E1.1.TIF CONSTRPLANS VIEW
020_E1.2.TIF CONSTRPLANS VIEW
002_S1.1.TIF CONSTRPLANS VIEW
003_S1.2.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW