Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T14BU01345
Permit Details
Apply Date:
12/05/2014
Applicant:
MATT BARNARD
Description:
FIRE SPKLR
Contractors:
- A 1 FIRE SPRINKLERS L L C
Outstanding Activity Conditions
Permit Number - T14BU01345
Permit Status: Expired
Permit Description: FIRE SPKLR
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
12/05/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T14BU01345
Permite Description: FIRE SPKLR
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2015 | FIRE SPKLR - FINAL | N/A | Denied | Correct sprinkler coverage in womens bathroom |
Completed Inspections
Permit Status: Expired
Permit Number: T14BU01345
Permit Description: FIRE SPKLR
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/10/2015 | FIRE SPKLR - OH PIPING & HYDRO | nsprenger | Approved | 208 PSI on both systems ( dry and preaction) for more than 2 hours. No leaks. Bled system pressure at main drain... water flowed out. |