Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2015 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Approved |
208 PSI on both systems ( dry and preaction) for more than 2 hours. No leaks. Bled system pressure at main drain... water flowed out. |
| 01/22/2015 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Partial Approval |
1. Partial for stainless steel 4'' riser and thrust block. Still need to hydro. Okay to backfill. |