Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
8989 E ESCALANTE RD
Apply Date:
10/21/2014
Applicant:
ANOZIRA FIRE PROTECTION L L C
Description:
FIXED SYSTEM
Contractors:
  • ANOZIRA FIRE PROTECTION L L C

Permit Reviews

Permit Number - T14BU01157
Permit Status: Final
Permit Description: FIXED SYSTEM
Start Date Submittal Complete Date Status  
10/21/2014 MECHANICAL 10/28/2014 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T14BU01157
Permit Status: Final
Permit Description: FIXED SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
10/21/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T14BU01157
Permit Description: FIXED SYSTEM
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/11/2014 FIRE - KITCHEN EXH HOOD FINAL CSCHULTZ Approved IFC 904.11.1 MANUAL OF OPERATION (PULL STATION) MIN OF 10' TO MAX OF 20' FROM HOOD SYSTEM right now pull station is 4' from hood system need to move it.
2. All electrical and gas shall shut down when system actives. (1) Outlet behind stove failed to shut down.

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW