Permit: T14BU01024
Permit Details
Status:
Final
Type:
COMMERCIAL OTHER
Address:
7050 S PALO VERDE RD
Address NEW:
7050 S PALO VERDE RD
Apply Date:
09/15/2014
Applicant:
CUTLER FIRE PROTECTION INC ,
Description:
1809 NEW SPRINKLERS
Contractors:
- CUTLER FIRE PROTECTION INC ,
Outstanding Activity Conditions
Permit Number - T14BU01024
Permit Status: Final
Permit Description: 1809 NEW SPRINKLERS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/15/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T14BU01024
Permit Description: 1809 NEW SPRINKLERS
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2015 | FIRE SPKLR - OH PIPING & HYDRO | nsprenger | Approved | Systems 1, 2, and 3 passed overhead hudrotest of 200 at 2 hrs. Held 210 psi at 3 + hours. sprinkler coverage is dropped under 16 rollup doors ( 2 heads per rollup door) STILL NEED: Branchline in the office hallway to be changed to pendants. Note for final - Swamp and Fans on floor look to be too close to some heads once they are installed ( systems 1, 2 and 3 ) only. |
| 07/21/2015 | FIRE SPKLR - UG PIPING FLUSH | CSCHULTZ | Approved | FLUSHED 2 MINS |
| 07/21/2015 | FIRE SPKLR - UG, PIPING, HYDRO | CSCHULTZ | Approved | |
| 10/22/2015 | FIRE SPKLR - FINAL | KENB | Approved |