Description:
1809 NEW SPRINKLERS
Contractors:
  • CUTLER FIRE PROTECTION INC ,

Outstanding Activity Conditions

Permit Number - T14BU01024
Permit Status: Final
Permit Description: 1809 NEW SPRINKLERS
Total Outstanding Activity Conditions - 1
Date Name
09/15/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T14BU01024
Permit Description: 1809 NEW SPRINKLERS
Total Completed Inspections - 4
Date Description Inspector Results Comments
01/21/2015 FIRE SPKLR - OH PIPING & HYDRO nsprenger Approved Systems 1, 2, and 3 passed overhead hudrotest of 200 at 2 hrs. Held 210 psi at 3 + hours.
sprinkler coverage is dropped under 16 rollup doors ( 2 heads per rollup door)
STILL NEED: Branchline in the office hallway to be changed to pendants.
Note for final - Swamp and Fans on floor look to be too close to some heads once they are installed ( systems 1, 2 and 3 ) only.
07/21/2015 FIRE SPKLR - UG PIPING FLUSH CSCHULTZ Approved FLUSHED 2 MINS
07/21/2015 FIRE SPKLR - UG, PIPING, HYDRO CSCHULTZ Approved
10/22/2015 FIRE SPKLR - FINAL KENB Approved