Permit: T14BU01024

Parcel: 14041867A

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T14BU01024

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
01/21/2015 FIRE SPKLR - OH PIPING & HYDRO Approved Systems 1, 2, and 3 passed overhead hudrotest of 200 at 2 hrs. Held 210 psi at 3 + hours.
sprinkler coverage is dropped under 16 rollup doors ( 2 heads per rollup door)
STILL NEED: Branchline in the office hallway to be changed to pendants.
Note for final - Swamp and Fans on floor look to be too close to some heads once they are installed ( systems 1, 2 and 3 ) only.
01/16/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Partial Approval ( tested systems #4 and #5 only)

passed 200 psi for 2 hours test

1) will need sprinkler coverage dropped under 16 rollup doors that are blocking an area when 'up' inexcess of 9 feet by 11.

2) Branch line in office hall way will be changed to pendants ( current uprights are touching insulation and wont have proper clearance).

NS 1/16/16