Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T14BU01024
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2015 | FIRE SPKLR - OH PIPING & HYDRO | Approved | Systems 1, 2, and 3 passed overhead hudrotest of 200 at 2 hrs. Held 210 psi at 3 + hours. sprinkler coverage is dropped under 16 rollup doors ( 2 heads per rollup door) STILL NEED: Branchline in the office hallway to be changed to pendants. Note for final - Swamp and Fans on floor look to be too close to some heads once they are installed ( systems 1, 2 and 3 ) only. |
|
| 01/16/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Partial Approval ( tested systems #4 and #5 only) passed 200 psi for 2 hours test 1) will need sprinkler coverage dropped under 16 rollup doors that are blocking an area when 'up' inexcess of 9 feet by 11. 2) Branch line in office hall way will be changed to pendants ( current uprights are touching insulation and wont have proper clearance). NS 1/16/16 |