Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T14BU00900
Permit Details
Apply Date:
08/12/2014
Applicant:
UNITED FIRE EQUIPMENT CO. **APA**
Description:
FIXED SYSTEM KITCHEN SUPPRESSION SYSTEM
Contractors:
- UNITED FIRE EQUIPMENT CO. **APA**
Permit Reviews
Permit Number - T14BU00900
Permit Status: Expired
Permit Description: FIXED SYSTEM KITCHEN SUPPRESSION SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/12/2014 | MECHANICAL | 08/26/2014 | COMPLETED |
| 12/16/2014 | REVISION - - 1ST | 12/23/2014 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T14BU00900
Permit Status: Expired
Permit Description: FIXED SYSTEM KITCHEN SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/12/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T14BU00900
Permite Description: FIXED SYSTEM KITCHEN SUPPRESSION SYSTEM
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2014 | FIRE - KITCHEN EXH HOOD FINAL | N/A | Partial Approval | Tested pull station, cut link, checked nozzles, check heights and laser shot aim points for nozzles, gas shut down, no electrical under hood all good except for the following: Need as built's for the changes made over the 6 burner stove approved plan shows 290 nozzles now changed to (3) 1F's Remove all wire nuts and extra wire out of the tank cabinet the tank cabinet is not approved for use as a J-box. |
Completed Inspections
Permit Status: Expired
Permit Number: T14BU00900
Permit Description: FIXED SYSTEM KITCHEN SUPPRESSION SYSTEM
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2014 | MECHANICAL - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |