Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T14BU00900
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2014 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | Tested pull station, cut link, checked nozzles, check heights and laser shot aim points for nozzles, gas shut down, no electrical under hood all good except for the following: Need as built's for the changes made over the 6 burner stove approved plan shows 290 nozzles now changed to (3) 1F's Remove all wire nuts and extra wire out of the tank cabinet the tank cabinet is not approved for use as a J-box. |
|
| 12/10/2014 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled | Showed up at schedualed time and the inspection could not be done due to kids sleeping in the daycare units. Called united and they never called me back to reschedual. |