Permit: T14BU00900

Parcel: 11522002A


Addresses:

1390 W SPEEDWAY BL


Inspection Status: Partial Approval

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00900

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
12/11/2014 FIRE - KITCHEN EXH HOOD FINAL Partial Approval Tested pull station, cut link, checked nozzles, check heights and laser shot aim points for nozzles, gas shut down, no electrical under hood all good except for the following:
Need as built's for the changes made over the 6 burner stove approved plan shows 290 nozzles now changed to (3) 1F's
Remove all wire nuts and extra wire out of the tank cabinet the tank cabinet is not approved for use as a J-box.
12/10/2014 FIRE - KITCHEN EXH HOOD FINAL Cancelled Showed up at schedualed time and the inspection could not be done due to kids sleeping in the daycare units. Called united and they never called me back to reschedual.