Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T14BU00889
Permit Details
Apply Date:
08/07/2014
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
- SIMPLEX GRINNELL L P
Outstanding Activity Conditions
Permit Number - T14BU00889
Permit Status: Final
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/07/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T14BU00889
Permit Description: FIRE ALARM
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2014 | FIRE - ALARM FINAL | CSCHULTZ | Approved | Sound system and projectors shut down when alarm activates -PASSED Duct smokes shut down and are set as supervisory - PASSED All doors to theaters close - PASSED Tested missing battery-PASSED Tested ground fault -PASSED Tested 3 pulls stations - PASSED Smoke above FACP - PASSED Radio communications - PASSED All horns/strobes - PASSED |