Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
08/07/2014
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
  • SIMPLEX GRINNELL L P

Outstanding Activity Conditions

Permit Number - T14BU00889
Permit Status: Final
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date Name
08/07/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T14BU00889
Permit Description: FIRE ALARM
Total Completed Inspections - 1
Date Description Inspector Results Comments
09/17/2014 FIRE - ALARM FINAL CSCHULTZ Approved Sound system and projectors shut down when alarm activates -PASSED
Duct smokes shut down and are set as supervisory - PASSED
All doors to theaters close - PASSED
Tested missing battery-PASSED
Tested ground fault -PASSED
Tested 3 pulls stations - PASSED
Smoke above FACP - PASSED
Radio communications - PASSED
All horns/strobes - PASSED

Documents

File Name Document Type  
001_ALARM.TIF FIRE PLANS VIEW
002_ALARM.TIF FIRE PLANS VIEW
003_ALARM.TIF FIRE PLANS VIEW
004_ALARM.TIF FIRE PLANS VIEW
005_ALARM.TIF FIRE PLANS VIEW
006_ALARM.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW