Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T14BU00889
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2014 | FIRE - ALARM FINAL | Approved | Sound system and projectors shut down when alarm activates -PASSED Duct smokes shut down and are set as supervisory - PASSED All doors to theaters close - PASSED Tested missing battery-PASSED Tested ground fault -PASSED Tested 3 pulls stations - PASSED Smoke above FACP - PASSED Radio communications - PASSED All horns/strobes - PASSED |
|
09/12/2014 | FIRE - ALARM FINAL | Denied | 1. Need to tie in duct detectors to Alarm panel. 2. Need Theater Sound System to shut down on Alarm Activation. |