Permit: T14BU00889

Parcel: 110113620

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T14BU00889

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2014 FIRE - ALARM FINAL Approved Sound system and projectors shut down when alarm activates -PASSED
Duct smokes shut down and are set as supervisory - PASSED
All doors to theaters close - PASSED
Tested missing battery-PASSED
Tested ground fault -PASSED
Tested 3 pulls stations - PASSED
Smoke above FACP - PASSED
Radio communications - PASSED
All horns/strobes - PASSED
09/12/2014 FIRE - ALARM FINAL Denied 1. Need to tie in duct detectors to Alarm panel.
2. Need Theater Sound System to shut down on Alarm Activation.