Permit: T14BU00802
Permit Details
Apply Date:
07/15/2014
Applicant:
ARMOR FIRE PROTECTION INC
Description:
KITCHEN FIRE SUPPRESSION SYSTEM
Contractors:
- ARMOR FIRE PROTECTION INC
Permit Reviews
Permit Number - T14BU00802
Permit Status: Expired
Permit Description: KITCHEN FIRE SUPPRESSION SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/15/2014 | MECHANICAL | 07/18/2014 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T14BU00802
Permit Status: Expired
Permit Description: KITCHEN FIRE SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/15/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T14BU00802
Permite Description: KITCHEN FIRE SUPPRESSION SYSTEM
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2014 | FIRE - KITCHEN EXH HOOD FINAL | N/A | Denied | 1) Pull station is 60 inches high - must be between 42 inches and 48 inches. 2.) Pull station is 6 feet from edge of hood - must be a minimum of 10 feet away and maximum of 20 feet away 3) Tighten up piping and adjust nozzles to aiming point. 4) There shall not be any wiring connections made inside of the ansul cabinet itself. It shall runt to an FM or UL listed junction box. 5) No pull was performed - need to do pull test |
Completed Inspections
Permit Status: Expired
Permit Number: T14BU00802
Permit Description: KITCHEN FIRE SUPPRESSION SYSTEM
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2014 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |