Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00802

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
12/30/2014 FIRE - KITCHEN EXH HOOD FINAL Denied 1) Pull station is 60 inches high - must be between 42 inches and 48 inches.
2.) Pull station is 6 feet from edge of hood - must be a minimum of 10 feet away and maximum of 20 feet away
3) Tighten up piping and adjust nozzles to aiming point.
4) There shall not be any wiring connections made inside of the ansul cabinet itself. It shall runt to an FM or UL listed junction box.
5) No pull was performed - need to do pull test