Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T14BU00802
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1) Pull station is 60 inches high - must be between 42 inches and 48 inches. 2.) Pull station is 6 feet from edge of hood - must be a minimum of 10 feet away and maximum of 20 feet away 3) Tighten up piping and adjust nozzles to aiming point. 4) There shall not be any wiring connections made inside of the ansul cabinet itself. It shall runt to an FM or UL listed junction box. 5) No pull was performed - need to do pull test |