Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
6951 S PARK AV
Address NEW:
6951 S PARK AV
Apply Date:
07/15/2014
Applicant:
WESTERN STATES FIRE PROTECTION C **APA**
Description:
NEW 365 FIRE SPRINKLERS FOR HANGER
Contractors:
  • WESTERN STATES FIRE PROTECTION C **APA**

Outstanding Activity Conditions

Permit Number - T14BU00794
Permit Status: Final
Permit Description: NEW 365 FIRE SPRINKLERS FOR HANGER
Total Outstanding Activity Conditions - 1
Date Name
07/15/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T14BU00794
Permit Description: NEW 365 FIRE SPRINKLERS FOR HANGER
Total Completed Inspections - 6
Date Description Inspector Results Comments
07/24/2014 FIRE SPKLR - UG PIPING FLUSH CBASALDU Approved
07/24/2014 FIRE SPKLR - UG, PIPING, HYDRO CBASALDU Approved
12/31/2014 FIRE SPKLR - FINAL CSCHULTZ Approved NEED AS BULTS FOR CHANGES AND CHANGE PER NEW APPROVED PLANS
01/07/2015 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved 200 psi test for 2 hours for new sprinkler piping - PASSED
01/07/2015 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved NEED TO DO 200 PSI TEST ON ALL NEW PIPING PER REVISED PLANS
01/07/2015 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved 200 PSI FOR 2 HOURS AND FLUSHED BOTH HOSE LINES