Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2015 | FIRE SPKLR - FINAL | Approved | Pre-action - PASSED 200 psi test for 2 hours for new sprinkler piping - PASSED Sprinkler piping changes per revised plans - APPROVED |
|
| 12/31/2014 | FIRE SPKLR - FINAL | Denied | NEED AS BULTS FOR CHANGES AND CHANGE PER NEW APPROVED PLANS | |
| 12/09/2014 | FIRE SPKLR - FINAL | Denied | NEED AS BULTS FOR CHANGES NEED TO ADD BRACES TO PIPING FOR THE HOSE LINES (SIDEWAYS) |