Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T14BU00794
Permit Details
Apply Date:
07/15/2014
Applicant:
WESTERN STATES FIRE PROTECTION C **APA**
Description:
NEW 365 FIRE SPRINKLERS FOR HANGER
Contractors:
- WESTERN STATES FIRE PROTECTION C **APA**
Outstanding Activity Conditions
Permit Number - T14BU00794
Permit Status: Final
Permit Description: NEW 365 FIRE SPRINKLERS FOR HANGER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/15/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T14BU00794
Permit Description: NEW 365 FIRE SPRINKLERS FOR HANGER
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2014 | FIRE SPKLR - UG PIPING FLUSH | CBASALDU | Approved | |
| 07/24/2014 | FIRE SPKLR - UG, PIPING, HYDRO | CBASALDU | Approved | |
| 12/31/2014 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | NEED AS BULTS FOR CHANGES AND CHANGE PER NEW APPROVED PLANS |
| 01/07/2015 | FIRE SPKLR - OH PIPING & HYDRO | CSCHULTZ | Approved | 200 psi test for 2 hours for new sprinkler piping - PASSED |
| 01/07/2015 | FIRE SPKLR - OH PIPING & HYDRO | CSCHULTZ | Approved | NEED TO DO 200 PSI TEST ON ALL NEW PIPING PER REVISED PLANS |
| 01/07/2015 | FIRE SPKLR - OH PIPING & HYDRO | CSCHULTZ | Approved | 200 PSI FOR 2 HOURS AND FLUSHED BOTH HOSE LINES |