Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
5602 E SPEEDWAY BL
Apply Date:
05/28/2014
Applicant:
ALL WEST FIRE PROTECTION SYSTEMS L L C
Description:
HOOD EXHAUST SYSTEM
Contractors:
  • ALL WEST FIRE PROTECTION SYSTEMS L L C

Permit Reviews

Permit Number - T14BU00562
Permit Status: Expired
Permit Description: HOOD EXHAUST SYSTEM
Start Date Submittal Complete Date Status  
05/28/2014 MECHANICAL 07/03/2014 COMPLETED Review Details
08/06/2014 MECHANICAL 08/06/2014 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T14BU00562
Permit Status: Expired
Permit Description: HOOD EXHAUST SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
05/28/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T14BU00562
Permite Description: HOOD EXHAUST SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
08/25/2014 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/25/2014 MECHANICAL - FINAL N/A Denied INTERLOCK MAKE UP AIR WITH EXHAUST EQUITMENT REPAIR BROKEN ELECT. CONDUITS ON ROOF. PROVIDE GREASE RECEPTARS AT EACH FAN. FANS NEED TO PROPERLY FIT THE ROOF CURBS ALL FANS NEED A DISCONNECTING MEANS THE CONNECTION TO THE UTILITY FAN IS BROKEN AT THE FLEXIBLE CONNECTION ONE OF THE SITILITY FANS & DUCT WORK IS NOT TYPE I RECOMMEND A LICENSED MECH CONTRACTOR TO GO THROUGH ALL EQUIPMENT & DETERMINE WHICH FANS ARE ABANDONED, MAKE ALL NECESSARY REPAIR REMOVE ALL ABANDONED EQUIPMENT FROM ROOF & CLEAN GREASE FROM ROOF

Completed Inspections

Permit Status: Expired
Permit Number: T14BU00562
Permit Description: HOOD EXHAUST SYSTEM
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/22/2014 FIRE - KITCHEN EXH HOOD FINAL wmotto Approved pending mechanical final