Permit: T14BU00562
Permit Details
Apply Date:
05/28/2014
Applicant:
ALL WEST FIRE PROTECTION SYSTEMS L L C
Description:
HOOD EXHAUST SYSTEM
Contractors:
- ALL WEST FIRE PROTECTION SYSTEMS L L C
Permit Reviews
Permit Number - T14BU00562
Permit Status: Expired
Permit Description: HOOD EXHAUST SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/28/2014 | MECHANICAL | 07/03/2014 | COMPLETED |
| 08/06/2014 | MECHANICAL | 08/06/2014 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T14BU00562
Permit Status: Expired
Permit Description: HOOD EXHAUST SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/28/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T14BU00562
Permite Description: HOOD EXHAUST SYSTEM
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2014 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 08/25/2014 | MECHANICAL - FINAL | N/A | Denied | INTERLOCK MAKE UP AIR WITH EXHAUST EQUITMENT REPAIR BROKEN ELECT. CONDUITS ON ROOF. PROVIDE GREASE RECEPTARS AT EACH FAN. FANS NEED TO PROPERLY FIT THE ROOF CURBS ALL FANS NEED A DISCONNECTING MEANS THE CONNECTION TO THE UTILITY FAN IS BROKEN AT THE FLEXIBLE CONNECTION ONE OF THE SITILITY FANS & DUCT WORK IS NOT TYPE I RECOMMEND A LICENSED MECH CONTRACTOR TO GO THROUGH ALL EQUIPMENT & DETERMINE WHICH FANS ARE ABANDONED, MAKE ALL NECESSARY REPAIR REMOVE ALL ABANDONED EQUIPMENT FROM ROOF & CLEAN GREASE FROM ROOF |
Completed Inspections
Permit Status: Expired
Permit Number: T14BU00562
Permit Description: HOOD EXHAUST SYSTEM
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2014 | FIRE - KITCHEN EXH HOOD FINAL | wmotto | Approved | pending mechanical final |