Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/25/2014 | MECHANICAL - FINAL | Denied | INTERLOCK MAKE UP AIR WITH EXHAUST EQUITMENT REPAIR BROKEN ELECT. CONDUITS ON ROOF. PROVIDE GREASE RECEPTARS AT EACH FAN. FANS NEED TO PROPERLY FIT THE ROOF CURBS ALL FANS NEED A DISCONNECTING MEANS THE CONNECTION TO THE UTILITY FAN IS BROKEN AT THE FLEXIBLE CONNECTION ONE OF THE SITILITY FANS & DUCT WORK IS NOT TYPE I RECOMMEND A LICENSED MECH CONTRACTOR TO GO THROUGH ALL EQUIPMENT & DETERMINE WHICH FANS ARE ABANDONED, MAKE ALL NECESSARY REPAIR REMOVE ALL ABANDONED EQUIPMENT FROM ROOF & CLEAN GREASE FROM ROOF |