Permit: T14BU00562

Parcel: 12703040B


Addresses:

5602 E SPEEDWAY BL

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/25/2014 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/25/2014 MECHANICAL - FINAL Denied INTERLOCK MAKE UP AIR WITH EXHAUST EQUITMENT REPAIR BROKEN ELECT. CONDUITS ON ROOF. PROVIDE GREASE RECEPTARS AT EACH FAN. FANS NEED TO PROPERLY FIT THE ROOF CURBS ALL FANS NEED A DISCONNECTING MEANS THE CONNECTION TO THE UTILITY FAN IS BROKEN AT THE FLEXIBLE CONNECTION ONE OF THE SITILITY FANS & DUCT WORK IS NOT TYPE I RECOMMEND A LICENSED MECH CONTRACTOR TO GO THROUGH ALL EQUIPMENT & DETERMINE WHICH FANS ARE ABANDONED, MAKE ALL NECESSARY REPAIR REMOVE ALL ABANDONED EQUIPMENT FROM ROOF & CLEAN GREASE FROM ROOF