Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T13CM06110
Permit Details
Apply Date:
10/04/2013
Applicant:
ORANGUTAN HOME SERVICES, INC *APA*
Description:
REPLACE 3 TON SPLIT SYSTEM (APA)
Contractors:
- ORANGUTAN HOME SERVICES, INC *APA*
Outstanding Activity Conditions
Permit Number - T13CM06110
Permit Status: Expired
Permit Description: REPLACE 3 TON SPLIT SYSTEM (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/04/2013 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T13CM06110
Permite Description: REPLACE 3 TON SPLIT SYSTEM (APA)
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
MECHANICAL - INTERMEDIATE | N/A | Not Inspected | ||
12/03/2013 | MECHANICAL - FINAL | N/A | Denied | - MAXIMUM FUSE OF 30 AMPS AT COMPRESSOR UNIT - LOCKOUTS NEEDED AT COMPRESSOR FOR LINESET - TRUSS REPAIR OR APPROVAL FROM ENGINEER FOR REMOVED WEB IN ATTIC TRUSSES - RE-ROUTE DUCT TO MAINTAIN MINIMUM WORKING DISTANCE IN FRONT OF UNIT |
12/03/2013 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |