Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T13CM06110
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
12/03/2013 | MECHANICAL - FINAL | Denied | - MAXIMUM FUSE OF 30 AMPS AT COMPRESSOR UNIT - LOCKOUTS NEEDED AT COMPRESSOR FOR LINESET - TRUSS REPAIR OR APPROVAL FROM ENGINEER FOR REMOVED WEB IN ATTIC TRUSSES - RE-ROUTE DUCT TO MAINTAIN MINIMUM WORKING DISTANCE IN FRONT OF UNIT |