Permit: T13CM02982
Permit Details
Apply Date:
05/16/2013
Applicant:
WATSON REFRIGERATION COMPANY INC
Description:
ADD 18 NEW A/C HEAT PUMPS
Contractors:
- WATSON REFRIGERATION COMPANY INC
Permit Reviews
Permit Number - T13CM02982
Permit Status: Final
Permit Description: ADD 18 NEW A/C HEAT PUMPS
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
05/16/2013 | COMMERCIAL - BLDG/FIRE/ZONING/ENG | 05/30/2013 | COMPLETED |
05/30/2013 | COMMERCIAL - BLDG/FIRE/ZONING/ENG | 05/30/2013 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T13CM02982
Permit Status: Final
Permit Description: ADD 18 NEW A/C HEAT PUMPS
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/16/2013 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T13CM02982
Permit Description: ADD 18 NEW A/C HEAT PUMPS
Total Completed Inspections - 8
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2013 | MECHANICAL - FINAL | JMILITEL | Approved | ROOFTOP CONDENSATE DRAINS DO NOT HAVE ADEQUATE SLOPE. PROVIDE AUDIBLE & VISIBLE ALRAMS FOR DUCT SMOKE DETECTORS AS PER SPECS. PROVIDE CLEANOUTS AS PER PLAN FOR CONDENSATE. TERMINATE CONDENSATE ABOVE FLOOD RIM OF SINKS. PROVIDE CO2 SENSORS AS PER PLAN. |
10/11/2013 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
03/25/2014 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | |
03/25/2014 | BUILDING - FINAL | JMILITEL | Approved | OK FOR FINAL, PENDING FIRE FINAL |
03/25/2014 | BUILDING - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
03/25/2014 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
04/08/2014 | FIRE - FINAL | DRAMIRE2 | Approved | IVRS - Inspection :* |
04/08/2014 | FIRE SPKLR - FINAL | DRAMIRE2 | Approved | IVRS - Inspection :* |