Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T13CM02982
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/25/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
03/07/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
03/07/2014 | MECHANICAL - FINAL | Partial Approval | - PROVIDE AIR BALANCE ON OUTSIDE AIR AS PER PLAN - PROVIDE A MIN 1" AIR GAP AT CONDENSATE DRAIN TERMINATION - EVERYTHING ELSE IS OK |
|
10/11/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
10/11/2013 | MECHANICAL - FINAL | Partial Approval | ROOFTOP CONDENSATE DRAINS DO NOT HAVE ADEQUATE SLOPE. PROVIDE AUDIBLE & VISIBLE ALRAMS FOR DUCT SMOKE DETECTORS AS PER SPECS. PROVIDE CLEANOUTS AS PER PLAN FOR CONDENSATE. TERMINATE CONDENSATE ABOVE FLOOD RIM OF SINKS. PROVIDE CO2 SENSORS AS PER PLAN. |