Permit: T13CM02655
Permit Details
Apply Date:
05/02/2013
Applicant:
ALASKAN HOME SERVICES INC
Description:
REPLACE 4 TON ROOFTOP GAS PACK
Contractors:
- ALASKAN HOME SERVICES INC
Outstanding Activity Conditions
Permit Number - T13CM02655
Permit Status: Expired
Permit Description: REPLACE 4 TON ROOFTOP GAS PACK
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/02/2013 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T13CM02655
Permite Description: REPLACE 4 TON ROOFTOP GAS PACK
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2013 | MECHANICAL - INTERMEDIATE | N/A | Denied | 1/2" PIPE AT 80' TDL WILL NOT SUPPLY 100,000 BTU. TEST NEW PIPING. SUPPORT PIPING TO WALL OR UNIT, WOOD SUPPORTS ON DIRT NOT ALLOWED. PROTECT CONDENSATE DRAIN CARBON MONOXIDE DETECTOR REQ. NOT A ROOF TOP UNIT. |
| 05/14/2013 | MECHANICAL - INTERMEDIATE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 05/14/2013 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |