Permit: T13CM02655

Parcel: 131050060


Addresses:

5418 E 29TH ST

Inspection Status: Denied

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
05/14/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/14/2013 MECHANICAL - INTERMEDIATE Denied 1/2" PIPE AT 80' TDL WILL NOT SUPPLY 100,000 BTU. TEST NEW PIPING. SUPPORT PIPING TO WALL OR UNIT, WOOD SUPPORTS ON DIRT NOT ALLOWED. PROTECT CONDENSATE DRAIN CARBON MONOXIDE DETECTOR REQ. NOT A ROOF TOP UNIT.