Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
06/27/2013
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
  • SIMPLEX GRINNELL L P

Outstanding Activity Conditions

Permit Number - T13BU00795
Permit Status: Final
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date Name
06/27/2013 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T13BU00795
Permit Description: FIRE ALARM
Total Completed Inspections - 1
Date Description Inspector Results Comments
10/16/2013 FIRE - ALARM FINAL CSCHULTZ Approved Only tested horns/strobes throughout building with system activated, with plans check all placement of pull stations, horns/strobes. Found 1 bad horn/strobe this was replaced during testing.
Still need to test all Saphires and dry-piping systems, tampers, flows, phone lines, battery loss, ground fault, missing devices, heats, duct smokes and smokes.
When testing the first Saphire system the following was found and all others are the same:
1. Need signs post per IFC and Saphire requirements i. e. on entry door over pull station etc.
2. When the Saphire system was activated the main alarm horns/strobes were bypass - only a blue color strobe was inside the Saphire room no horn, you will need to have a horn for the Saphire system that is different them the main fire alarm system and has a count down and activated sound.
3. Will need to have an air loss calculation test done on the rooms were the Saphire are installed.
4. All ceiling tiles in Saphire rooms need to be tied down
5. All doors going in and out of the Saphire rooms need to be self-closing and latching
6. Need to change out all pull stations to the Saphire systems or install a sign above the pull stations, ID then as Saphire system cannot use a fire alarm pull station only this will be very confusing to people.

Documents

File Name Document Type  
001_ALARM.TIF FIRE PLANS VIEW
002_ALARM.TIF FIRE PLANS VIEW
003_ALARM.TIF FIRE PLANS VIEW
004_ALARM.TIF FIRE PLANS VIEW
005_ALARM.TIF FIRE PLANS VIEW
006_ALARM.TIF FIRE PLANS VIEW
007_ALARM.TIF FIRE PLANS VIEW
008_ALARM.TIF FIRE PLANS VIEW
009_ALARM.TIF FIRE PLANS VIEW
010_ALARM.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW