Permit: T13BU00795

Parcel: 14041009A


Addresses:

3350 E VALENCIA RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T13BU00795

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/13/2014 FIRE - ALARM FINAL Approved
03/10/2014 FIRE - ALARM FINAL Not ready for Inspection 1. everything is tested and passed.
2. all signals must be monitored off site we need to check to see if smokes, pullstations are being monitored off site.
3. all sprinkler system components such as tampers and water flows are supervised off site.
4. we need to verify that every tile in clean agent rooms are properly clipped.
10/16/2013 FIRE - ALARM FINAL Denied Only tested horns/strobes throughout building with system activated, with plans check all placement of pull stations, horns/strobes. Found 1 bad horn/strobe this was replaced during testing.
Still need to test all Saphires and dry-piping systems, tampers, flows, phone lines, battery loss, ground fault, missing devices, heats, duct smokes and smokes.
When testing the first Saphire system the following was found and all others are the same:
1. Need signs post per IFC and Saphire requirements i. e. on entry door over pull station etc.
2. When the Saphire system was activated the main alarm horns/strobes were bypass - only a blue color strobe was inside the Saphire room no horn, you will need to have a horn for the Saphire system that is different them the main fire alarm system and has a count down and activated sound.
3. Will need to have an air loss calculation test done on the rooms were the Saphire are installed.
4. All ceiling tiles in Saphire rooms need to be tied down
5. All doors going in and out of the Saphire rooms need to be self-closing and latching
6. Need to change out all pull stations to the Saphire systems or install a sign above the pull stations, ID then as Saphire system cannot use a fire alarm pull station only this will be very confusing to people.