Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
06/06/2013
Applicant:
COLLINS EXCAVATING AND MATERIALS INC
Description:
FIRE UNDERGROUND PIPING
Contractors:
  • COLLINS EXCAVATING AND MATERIALS INC

Outstanding Activity Conditions

Permit Number - T13BU00688
Permit Status: Final
Permit Description: FIRE UNDERGROUND PIPING
Total Outstanding Activity Conditions - 1
Date Name
06/06/2013 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T13BU00688
Permit Description: FIRE UNDERGROUND PIPING
Total Completed Inspections - 2
Date Description Inspector Results Comments
06/12/2013 FIRE SPKLR - UG, PIPING, HYDRO WMOTTO Approved did 200 psi on fire riser pipe stub.
Ifc 2012 section 914.3.1.2 water supply to required fire pumps.
required fire pumps shall be supplied by connections to a minimum of two water mains located in different streets. seperate supply piping shall be provided between each connection to water main and the pumps each connectionand the supply piping between the connections and the pumps shall be sized to supply the flow and pressure required for pumps to operate.
handout was given to contractor with this code and the exceptions.
07/31/2014 FIRE SPKLR - UG PIPING FLUSH kenb Approved

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW