Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T13BU00688

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2014 FIRE SPKLR - UG, PIPING, HYDRO Approved
04/01/2014 FIRE SPKLR - UG, PIPING, HYDRO Denied Tested both undergrounds failed to hold.
06/12/2013 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval did 200 psi on fire riser pipe stub.
Ifc 2012 section 914.3.1.2 water supply to required fire pumps.
required fire pumps shall be supplied by connections to a minimum of two water mains located in different streets. seperate supply piping shall be provided between each connection to water main and the pumps each connectionand the supply piping between the connections and the pumps shall be sized to supply the flow and pressure required for pumps to operate.
handout was given to contractor with this code and the exceptions.