Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
3350 E VALENCIA RD
Apply Date:
05/31/2013
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE SPRINKLER PERMIT
Contractors:
  • SIMPLEX GRINNELL L P

Outstanding Activity Conditions

Permit Number - T13BU00634
Permit Status: Final
Permit Description: FIRE SPRINKLER PERMIT
Total Outstanding Activity Conditions - 1
Date Name
05/31/2013 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T13BU00634
Permit Description: FIRE SPRINKLER PERMIT
Total Completed Inspections - 2
Date Description Inspector Results Comments
10/16/2013 FIRE SPKLR - FINAL CSCHULTZ Approved 1. Analytical Lab shower need sprinkler coverage X2
2. Chem storage room correct coverage 8' 6" off wall
3. Mineralogy - high grade room correct sprinkler coverage 8' 6" off wall
4. Mineralogy - Mid grade room correct sprinkler coverage 8' 6" off wall
In corridor (on plans S-46 next to personnel space, submittal office, supervisor office) correct sprinkler coverage
5. Mineralogy north correct sprinkler coverage in shower
6. East corridor area C (by Qemscam rm, Util Chase rm, XRD Lab rm) correct sprinkler coverage heads 20' feet apart
7. Hydro test all new piping installed for the dry system for 2 hours at 200 PSI.
03/10/2014 FIRE SPKLR - OH PIPING & HYDRO wmotto Approved