Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13BU00634
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/10/2014 | FIRE SPKLR - FINAL | Approved | ||
10/16/2013 | FIRE SPKLR - FINAL | Denied | 1. Analytical Lab shower need sprinkler coverage X2 2. Chem storage room correct coverage 8' 6" off wall 3. Mineralogy - high grade room correct sprinkler coverage 8' 6" off wall 4. Mineralogy - Mid grade room correct sprinkler coverage 8' 6" off wall In corridor (on plans S-46 next to personnel space, submittal office, supervisor office) correct sprinkler coverage 5. Mineralogy north correct sprinkler coverage in shower 6. East corridor area C (by Qemscam rm, Util Chase rm, XRD Lab rm) correct sprinkler coverage heads 20' feet apart 7. Hydro test all new piping installed for the dry system for 2 hours at 200 PSI. |
|
09/27/2013 | FIRE SPKLR - FINAL | Denied | 1. Need to relocate 2 sprinkler heads in environmental room for Phase 2 work. |