Permit: T13BU00634
Permit Details
Apply Date:
05/31/2013
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE SPRINKLER PERMIT
Contractors:
- SIMPLEX GRINNELL L P
Outstanding Activity Conditions
Permit Number - T13BU00634
Permit Status: Final
Permit Description: FIRE SPRINKLER PERMIT
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/31/2013 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T13BU00634
Permit Description: FIRE SPRINKLER PERMIT
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2013 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | 1. Analytical Lab shower need sprinkler coverage X2 2. Chem storage room correct coverage 8' 6" off wall 3. Mineralogy - high grade room correct sprinkler coverage 8' 6" off wall 4. Mineralogy - Mid grade room correct sprinkler coverage 8' 6" off wall In corridor (on plans S-46 next to personnel space, submittal office, supervisor office) correct sprinkler coverage 5. Mineralogy north correct sprinkler coverage in shower 6. East corridor area C (by Qemscam rm, Util Chase rm, XRD Lab rm) correct sprinkler coverage heads 20' feet apart 7. Hydro test all new piping installed for the dry system for 2 hours at 200 PSI. |
03/10/2014 | FIRE SPKLR - OH PIPING & HYDRO | wmotto | Approved |