Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
8532 E 18TH ST
Address NEW:
8532 E 18TH ST
Apply Date:
01/09/2012
Applicant:
RICK TURNER
Description:
REPL SPLIT WITH PACKAGE ROOFTOP HEAT PUMP
Contractors:
  • DART ENTERPRISES LLC

Permit Reviews

Permit Number - T12ME00002
Permit Status: Expired
Permit Description: REPL SPLIT WITH PACKAGE ROOFTOP HEAT PUMP
Start Date Submittal Complete Date Status  
01/09/2012 MECHANICAL 01/09/2012 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T12ME00002
Permit Status: Expired
Permit Description: REPL SPLIT WITH PACKAGE ROOFTOP HEAT PUMP
Total Outstanding Activity Conditions - 1
Date Name
01/09/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T12ME00002
Permite Description: REPL SPLIT WITH PACKAGE ROOFTOP HEAT PUMP
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
01/20/2012 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection :*
01/20/2012 MECHANICAL - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/20/2012 MECHANICAL - FINAL N/A Not ready for Inspection IVRS - Inspection :*
1) ALL DUCT EXPOSED TO EXTERIOR IS TO HAVE MINIMUM R-8 INSULATION (2" LINER) (1" LINER CANNOT BE ADDED TO EXISTING 1" LINER)
2) ALL PVC PIPE JOINTS AND FITTINGS ARE TO HAVE PRIMER PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR PER UPC
3) ALL PVC EXPOSED TO DAY LIGHT IS TO BE COATED FOR U.V. PROTECTION. PVC BLOCKING MAX DISTANCE 48"
4) UNIT NOT SUPPORTED PER PLANS
5) PROVIDE SERVICE OUTLET PER PLANS
6) BLOCK ELECTRIC CONDUIT UP OFF OF ROOF (SEAL-TITE)
7) NEED TO VERIFY ELECTRICAL LOAD CALC

Documents

File Name Document Type  
None CONSTRPLANS VIEW
None DOCUMENTS VIEW