Permit: T12ME00002

Parcel: 134080900


Addresses:

8532 E 18TH ST

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/20/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) ALL DUCT EXPOSED TO EXTERIOR IS TO HAVE MINIMUM R-8 INSULATION (2" LINER) (1" LINER CANNOT BE ADDED TO EXISTING 1" LINER)
2) ALL PVC PIPE JOINTS AND FITTINGS ARE TO HAVE PRIMER PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR PER UPC
3) ALL PVC EXPOSED TO DAY LIGHT IS TO BE COATED FOR U.V. PROTECTION. PVC BLOCKING MAX DISTANCE 48"
4) UNIT NOT SUPPORTED PER PLANS
5) PROVIDE SERVICE OUTLET PER PLANS
6) BLOCK ELECTRIC CONDUIT UP OFF OF ROOF (SEAL-TITE)
7) NEED TO VERIFY ELECTRICAL LOAD CALC