Permit: T12CM07868
Permit Details
Status:
Expired
Type:
SOLAR WAIVER - RES
Address:
8650 E WOODLAND RD
Address NEW:
8650 E WOODLAND RD
Apply Date:
12/13/2012
Applicant:
VALLEY WIDE ELECTRIC CO L L C
Description:
ROOF MOUNT SOLAR SYSTEM AND NEW SES SOLAR READY ELECTRICAL PANEL. THIS IS FOR THE HOUSE, BARN ALREADY ISSUED.
Contractors:
- VALLEY WIDE ELECTRIC CO L L C
Permit Reviews
Permit Number - T12CM07868
Permit Status: Expired
Permit Description: ROOF MOUNT SOLAR SYSTEM AND NEW SES SOLAR READY ELECTRICAL PANEL. THIS IS FOR THE HOUSE, BARN ALREADY ISSUED.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/02/2013 | RESIDENTIAL - BLDG/ZONING/ENGINE/WWM | 01/23/2013 | COMPLETED |
| 02/22/2013 | REVISION - - 1ST | 02/22/2013 | COMPLETED |
| 12/13/2012 | PLANS OK TO SUBMIT - RES | 12/13/2012 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T12CM07868
Permit Status: Expired
Permit Description: ROOF MOUNT SOLAR SYSTEM AND NEW SES SOLAR READY ELECTRICAL PANEL. THIS IS FOR THE HOUSE, BARN ALREADY ISSUED.
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/13/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T12CM07868
Permite Description: ROOF MOUNT SOLAR SYSTEM AND NEW SES SOLAR READY ELECTRICAL PANEL. THIS IS FOR THE HOUSE, BARN ALREADY ISSUED.
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2013 | BUILDING - FINAL | N/A | Denied | 1. MAINTAIN WORKING SPACE AT PV PANEL 110.26 2. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICES 3. TIGHTEN LOOSE FITTINGS & LUGS 4. NEED LABEL AT COMBINER PANEL (90.1) 5. DATA BOX AND INTERIOR PLUG STRIP NOT LISTED 6. USE APPROVED GROUNDING TERMINATIONS FOR WEEB SYSTEM 690.41-43 7. SECURE DC CONNECTORS UP UNDER MODULES 8. SECURE SUPPORTS TO ROOF WITH SEALANT 9. PLANS CALL FOR 80A PV INTERCONNECT BREAKER 150A INSTALLED |
| 05/09/2013 | BUILDING - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
Completed Inspections
Permit Status: Expired
Permit Number: T12CM07868
Permit Description: ROOF MOUNT SOLAR SYSTEM AND NEW SES SOLAR READY ELECTRICAL PANEL. THIS IS FOR THE HOUSE, BARN ALREADY ISSUED.
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2013 | ELECTRIC - SERVICE UPGRADE | DQUINN | Approved | IVRS - Inspection :* |
| 06/06/2013 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* |
| 06/07/2013 | TEP CLEARANCE - AM | RMORENO | Approved | OK TO ENERGIZE DGC SOLAR PANEL FINAL RES 1 METER |