Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
1775 W SAHUARO DR
Apply Date:
11/02/2012
Applicant:
ZANE LEIBER
Description:
GAS SERVICE TO NEW FURNANCE
Contractors:
  • LEIBER CUSTOM HOMES L L C

Permit Reviews

Permit Number - T12CM07011
Permit Status: Final
Permit Description: GAS SERVICE TO NEW FURNANCE
Start Date Submittal Complete Date Status  
11/02/2012 WALK THRU - COMM 11/02/2012 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T12CM07011
Permit Status: Final
Permit Description: GAS SERVICE TO NEW FURNANCE
Total Outstanding Activity Conditions - 1
Date Name
11/02/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T12CM07011
Permit Description: GAS SERVICE TO NEW FURNANCE
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/12/2012 PLUMBING - INTERMEDIATE RMYERS Approved 1. Plan shows 2PSIG at the meter. Is this a medium pressure system? If so, the test is to 60 pounds. Not installed per plan. Plan not accurate. Provide an accurate isometric showing the "as built" installation. Show developed length and total BTU consumption of each appliance. Roof top gas not supported per table 3-2 2006 UPC. Re-use of gas piping not permitted. Thread protectors are not approved couplings. Use std. taper threaded couplings. Black iron pipe may not be installed underground. Black iron pipe may not be directly embedded in concrete. Require a ladder for access to the second building. Require a bond between gas and electric. Require sediment traps. Underground piping covered with out inspection.
01/31/2013 PLUMBING - FINAL RMYERS Approved 1) CORRECTIONS MADE OK FOR GAS

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW