Permit: T12CM06251
Permit Details
Status:
Final
Type:
COMMERCIAL OTHER
Address:
1844 W SAN MARCOS BL
Address NEW:
1844 W SAN MARCOS BL
Apply Date:
10/05/2012
Applicant:
JOSE LUIS PACHECO
Description:
COMMERCIAL REWIRE AND RECONNECT
Contractors:
- TOMAHAWK ELECTRIC INC *APA*
Permit Reviews
Permit Number - T12CM06251
Permit Status: Final
Permit Description: COMMERCIAL REWIRE AND RECONNECT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/12/2012 | COMMERCIAL - TI | 12/14/2012 | ACTIVE |
Outstanding Activity Conditions
Permit Number - T12CM06251
Permit Status: Final
Permit Description: COMMERCIAL REWIRE AND RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/05/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T12CM06251
Permit Description: COMMERCIAL REWIRE AND RECONNECT
Total Completed Inspections - 11
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2012 | ELECTRIC - RECONNECT | DSANTACR | Approved | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE APPROVED PLANS AND PERMIT FOR NEW WIRING, PANELS, SERVICE EQUIP, INSIDE AND OUT. INCLUDE MECH, PLUMBING, STRUCTURE. BLD IS GUTTED OUT AT THIS TIME. YOU MAY OBTAIN TEMP POWER UNDER T.I. PERMIT, IF ELECT. MEETS CODE. USE LICENSED OR QUALIFIED ELECTRICAL. |
| 03/20/2013 | ELECTRIC - SERVICE UPGRADE | DSANTACR | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. PLUF UNUSED OPENING IN METER ENCLOSURE. 2. INSTALL BOND BUSHING BETWEEN METER BASE AND MAIN SERVICE DISC. SW. INSTALL R-PINS FOR FUSES. 3.SUPPORT # BARE GROUND TO STRUCTURE. 4. BOND WATE AND GAS PIPING 5. J-BOXES NEED TO HAVE CONDUCTORS TERMINATED OR CAPPED OFF. 6. CONTR. TO VERIFY 2X4 LAYING LIGHT FIXTURES LISTING COMPLIES WITH INSTALLATIONS. IT MAY NOT BE PERMISSIBLE FOR LIGHT FIXTURE TO BE SECURED TO COMBUSTIBLE MATERIAL |
| 07/12/2013 | TEP CLEARANCE - AM | DSANTACR | Approved | TEC |
| 11/15/2013 | SHEET ROCK NAILING | RCAMACHO | Approved | IVRS - Inspection :* |
| 03/19/2014 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* |
| 03/19/2014 | FRAMING | DSANTACR | Approved | IVRS - Inspection :* |
| 03/31/2014 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | PER ELEC FINAL |
| 03/31/2014 | OUTDOOR LIGHTING FINAL | DSANTACR | Approved | IVRS - Inspection :* |
| 03/31/2014 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
| 03/31/2014 | ELECTRIC - OUTDOOR LIGHTING | DSANTACR | Approved | IVRS - Inspection :* |
| 03/31/2014 | BUILDING - FINAL | DSANTACR | Approved | IVRS - Inspection :* |